- Broad Temperature Range from -70° C to 150° C *with optional heater
- Copeland Compressors for advanced HVACR applications
- Connect to controller software via WiFi connection or Ethernet
- 19 liter stainless steel fluid reservoir
- 1 year parts & labor warranty
Custom Options
- Heating Circuit
- Water-Cooled Condenser
- Pass Through Systems
- Extended Ambient Package for Cold Climate
Dimensions |
Weight |
522kg (1150 lbs)
|
Dimensions (L x W x H) |
91 x 135 x 165 cm (36 x 53 x 65 in)
|
Performance |
Working Temperature Range |
-70° C to 150° C with optional heater (-94° F to 302° F)
|
Temperature Stability |
±2° C
|
Cooling Capacity @ 21° C |
-70° C (-94° F) - 1,500 W (5,118 BTU/hr)
-60° C (-76° F) - 2,900 W (9,895 BTU/hr)
-40° C (-40° F) - 3,200 W (10,918 BTU/hr)
0° C (32° F) - 3,200 W (10,918 BTU/hr)
|
Heater Capacity |
3,500 W (11,942 BTU/hr)
|
Pump Performance |
4.5 GPM @ 50 PSI
|
User Interface |
Controls |
Electronic Programmed Temperature Controller with Constant
(Set Point & Process)
|
Additional Features |
Fluid Level Indicator
|
Refrigeration Circuit |
Compressor |
Copeland Scroll
|
Heat Exchanger |
Stainless Steel Brazed Plate Heat Exchangers
|
Refrigerant |
R404a/R508b
|
Additional Features |
Access Ports, Service Valves, Filter Drier, Sight Glass, Liquid Receiver,
Thermostatic Expansion
|
Max Heat Rejection |
9,200 W (31,450 btu/hr)
|
Process Fluid Circuit |
Pump |
Continuous Duty, 0.75 kW Vortex Pump
|
Inlet/Outlet |
3/4” NPT
|
Reservoir |
19 L (5 gal) Stainless Steel
|
Additional Features |
Inline Strainer, Inlet and Outlet Temperature Sensors, Pump Discharge
Pressure Transducer, N2 Blanket for Moisture Prevention
|
Construction |
Frame |
Galvanized Steel
|
Enclosure |
Powder Coated Steel Enclosure with Easy Access Panels
|
Quality |
Warranty |
1 Year Standard Warranty
|
UL/CSA Certified (Full Assembly) |
ETL 3170655, UL STD 61010-2-011, CAN/CSA STD,
C22.2 No. 61010-2-011
|
Manufacturing |
Manufactured in the U.S.A.
|
Power |
Avaiable Voltages |
208-240VAC / 3P / 60Hz
208-240VAC / 1P / 60Hz
480VAC / 3P / 60Hz 50Hz and other voltages available on request
|
Max Amps (FLA) |
25 Amps
|
Recommended Breaker/Service (MCA) |
30 Amps
|
Heat Transfer Fluid Options (Sold Separately): NOVEC 7500, Syltherm, Paratherm LR, Paratherm CR, Fragoltherm, and more.
Product Brochures
Ascent ULT Chillers Brochure
Drawings
Ascent 1000 Series Ultra-Low Temperature Chillers Spec Sheet